TESTING SCHEDULE

 

#

Equipment / Premises

Scope of Testing

Rules and Regulations

Frequency

1

Power supply networks, electric protective and other devices in medium or low risk premises

Visual check

Acc. to maintenance schedule

Resistance measurement in cable insulation

Rules for Operating Consumer Electrical Equipment (ПТЭЭП) 2.12.17; Rules for Operating Consumer Electrical Equipment (ПТЭЭП), Annex 3.1, Tab. 37

At least once every three years

At least once a year in high risk8.3 premises and outdoor equipment8.4

Protective conductor (contact resistance measurement)

Rules for Operating Consumer Electrical Equipment (ПТЭЭП), Annex 3, P.28.5

Acc. to maintenance schedule (overhaul, routine and corrective repairs) after testing of automatic protection system

Phase-neutral loop impedance (protection check)

Rules for Operating Consumer Electrical Equipment (ПТЭЭП) P.2.7.17; Rules for Operating Consumer Electrical Equipment (ПТЭЭП), Annex 3, P.28.4

After assembling new electric lines and installing new equipment, acc. to maintenance schedule (overhaul, routine and corrective repairs)

Residual-current device (RCD)

Rules for Operating Consumer Electrical Equipment (ПТЭЭП), Annex 3, P.28.7.

At least once every three months

Thermal and magnetic trips

Rules for Operating Consumer Electrical Equipment (ПТЭЭП), Annex 3, P.28.6.

Electric unit/equipment commissioning, acc. to maintenance schedule (overhaul)


2

Electric power equipment in high risk premises including explosive atmosphere (Electrical Installation Rules (ПУЭ) 7 P.7.3.22)10, with up to 1000W voltage and solid grounding (TN system)

Phase-neutral loop impedance of a consuming unit connected to each line and switchboard; short-circuit current calculated to ensure reliability of electric protection system

Rules for Operating Consumer Electrical Equipment (ПТЭЭП) P.3.4.12

At least once every two years

Electrical protection system failure

3

Retail premises

Resistance in cable insulation

ПОТ РМ-014-2000 Retail Industries Labor Safety Rules 8.5.18, Rules for Operating Consumer Electrical Equipment (ПТЭЭП), Annex 3 Tab. 37

At least once a year for low risk8.1 premises

At least once in six months in high risk8.3 or medium risk8.2 premises

Protective ground (bonding)

ПОТ РМ-014-2000 Retail Industries Labor Safety Rules P.8.5.18

At least once a year

Lighting:

standby lighting

At least once a month (daytime)

standby lighting automation in failure of main lighting system

At least twice a year


4

Catering equipment (inc. stoves and ovens); chemical cleaning and washing equipment

Resistance in cable insulation

ПОТ РМ-011-2000 Food Service Industry Labor Safety Rules P.5.6; ПОТ РМ-013-2000 Labor Safety in Chemical Cleaning and Washing P. 3.8.37; Rules for Operating Consumer Electrical Equipment (ПТЭЭП), Annex 3, Tab. 37

At least once a year for low risk8.1 premises

At lest once in six month for high risk8.3 or medium risk8.2 premises

Protective ground (bonding)

At least once a year

5

Power equipment in medical premises

Automatic changeover switch to emergency power supply

GOST R 50571.28-2006: Power Equipment in Medical Premises (МЭК 60364-7-710:2002), P. 710.62 (P. a-h)

At least once a year

Insulation resistance control sensor

Visual check of devices settings

RCD cut-out testing by residual current check

Bonding check

At least once every three years

6

Lifting mechanisms (loaders, elevators and etc.)

Insulation resistance

Rules for Operating Consumer Electrical Equipment (ПТЭЭП), Annex 3.1, Tab. 37

At least once a year

7

Lightning protection system

Lightning protection system check

Lightning Protection Regulations РД 34.21.122-87 P.1.14.; РД 153 34.0-20525-00 P.1.4.

For Class I and Class II lightning protection systems9 before thunderstorm season begins

At least once every three years for Class III lightning protection systems9

Lightning protection of plumbing system

Safety Rules for Operating Air and Flue Ducts ПБ03-445-02 Sec. 3 P. 15 dated 03 December, 2001, #56

Annually before thunderstorm season begins

8

Grounding

Touch voltage measurement

РД 153 34.0-20525-00 P.1.4., ПОТ РМ-021-2002 Labor Safety in Operating Oil and Lubricants Storage Facilities, and Mobile or Stationary Fuel Stations P. 5.3.14.

At least once every six years (except for specific category premises: once a year for fuel and lube storage facilities of Class I and Class II; and at least once every three years for Class III fuel and lube storage facility

Visual check with opening

At least once every 12 years

Quick-break fuse and phase-neutral loop

At least once every six years

Notes:

1    Electrical Installation Rules (ПУЭ) 1.1.6. DRY LOCATION is the premise where relative humidity of 60% is not exceeded. In case the conditions specified in paragraphs 1.1.10 - 1.1.12 do not characterize the premises, they are considered normal.

2    Electrical Installation Rules (ПУЭ) 1.1.7. HUMID LOCATION is the premise where relative humidity reaches 60% but does not exceed 75%.

3    Electrical Installation Rules (ПУЭ) 1.1.8. DAMP LOCATION is the premise where relative humidity exceeds 75%.

4    Electrical Installation Rules (ПУЭ) 1.1.9. EXTREMELY HUMID LOCATION is the premise where relative humidity is close to 100% (ceiling, walls, floor, furniture and other property items are weeping).

5    Electrical Installation Rules (ПУЭ) 1.1.10. HOT PREMISE is the premise where ambient temperature occasionally (for over 24 hours) or permanently exceeds +35ºС (i.e. premises where ovens, dryers or boilers are installed).

6    Electrical Installation Rules (ПУЭ) 1.1.11. DUST-LOADED PREMISE is the premise where due to occupational factor dust is emitted and covers current-carrying parts or penetrates inside the tools and equipment. Premises exposed to conductive and nonconductive dust are distinguished.

7    Electrical Installation Rules (ПУЭ) 1.1.12. PREMISES WITH CHEMICALLY ACTIVE OR ORGANIC MEDIA, where, occasionally or permanently, aggressive gases or fluids, as well as mold or other deposits are formed and destroy insulation and current-carrying parts of electrical equipment.

8     Electrical Installation Rules (ПУЭ) 1.1.13 provide several categories of electrical hazard:

      1) Low Risk Premises without the conditions which produce high or medium hazard (see paragraphs 2 and 3).

      2) High Risk Premises are characterized by at least one of the following:

- humidity or conductive dust (see paragraphs 1.1.8 and 1.1.11)

- conductive flooring (metal, dirt, ferro-concrete, brick and other materials)

- high temperature (see P. 1.1.10)

- safety of touching a grounded metal structure or electrical installation while simultaneously touching the metal casing of power equipment (open current-carrying parts)

      3) Extremely Hazardous Premises are characterized by at least one of the following:

          - very high humidity (see P. 1.1.9)

          - chemically active or organic media (see P. 1.1.12)

          - two or more types of hazard affecting the same premise (see P. 1.1.13 item 2)

      4) Areas containing exposed electrical components refer to the category of Extremely Hazardous Premises.

9    Lightning Protection Regulations РД 34.21.122-87 P. 1.2.

      Class I and Class II lightning protection systems prevent buildings and structures from direct lightning strikes and their secondary effects including transients through the metal components of surface and underground supply lines.

      Class III lightning protection systems prevent buildings and structures from direct lightning strikes and transients through the metal components of surface supply lines. Outdoor equipment fitted with Class II lightning protection system is prevented from direct lightning strikes and their secondary effects. Indoor equipment installed within large areas (over 100 meters in width) requires minimized voltage differential (equal electrical potential / equipotential bonding).

10   Electrical Installation Rules (ПУЭ) 7.3.22. Explosive Atmosphere refers to areas (premises or outdoor equipment) containing or producing explosive substances.

1